8 031 1 start up sheet condensing unit

START-UP SHEET Condensing Unit

Job Name ____ Job Number ____

Job Address ____

Section 5: Equipment Description

Spec. #: Submittal #: P&ID/Dwg #:
Area Served:
Data Design Actual On Site
Unit Tag #
Manufacturer
Model #
Serial #
Refrigerant Type
Refrigerant Quantity(lbs.)

Section 6: Equipment Pre-Installation Inspection

Step Inspection Description Yes No N/A Performed By(Initials & Date)
6.2 Nameplate data matches vendor specifications. □ ⊗ □
6.3 All parts are received. □ □ □
6.4 No visible signs of damage, leak, or defective parts. □ □ □
6.5 Verify electrical service for correct voltage, current and thermal overload protection. □ □ □
6.6 Operational and Maintenance(O&M) manual is available in field. □ □ □
6.7 Start-up technicians have reviewed factory start-up procedures in O&M manual. □ □ □

Comments/ Observations


Performed (Therma)

By

Reviewed By (Owner/Representatives)

Print Name Signature Date

Section 7: Installation Inspection

ID Inspection Description Yes No N/A Performed By (Initials & Date)
7.2 Unit is installed level. □ □ □
7.3 Tag # is attached to the unit. □ □ □
7.4 Service clearance is adequate for maintenance. □ □ □
7.5 Vibration isolators are installed and adjusted. □ □ □
7.6 All compressor shipping braces and compressor rail isolator sleeves are removed. □ □ □
7.7 Compressor oil level is within manufacturer’s specification. □ □ □
7.8 Liquid line drier is installed properly. □ □ □
7.9 Suction line(s) is properly sized and installed. □ □ □
7.10 Liquid line(s) and Hot Gas Bypass line(s) is sized and installed. □ □ □
7.11 Suction and Hot Gas Bypass line(s) are insulated. □ □ □
7.12 All condenser fan setscrews are tight. □ □ □
7.13 Coils are clean & fins are straight. □ □ □
7.14 Low ambient control is installed. □ □ □
7.15 All bearings are lubricated. □ □ □
7.16 Piping has undergone pressure test □ □ □
7.17 Piping is clamped and isolated. □ □ □
7.18 Piping is labeled. □ □ □
7.19 Crankcase heaters are installed. □ □ □
7.20 Electrical connections are secure. □ □ □
7.21 All access panels and covers are in place. □ □ □

Performed By (Therma)

Reviewed By (Owner/Representatives)

Print Name Signature Date

Section 8: Operational Inspection

ID Inspection Description Yes No N/A Performed By(Initials & Date)
8.2 Unit vibration is acceptable. $$ $$ $$
8.3 Fan rotation is correct. $$ $$ $$
8.4 Crankcase heaters are functional. $$ $$ $$
8.5 Cooling components perform per manufacturer's specifications. $$ $$ $$
8.6 Make sure thermostat is set. $$ $$ $$
8.7 Record start up operating parameters in the Supplementary Forms(FN 8.028.2 or FN 8.028.3).

End of Section

Comments/

Observations

Performed By

(Therma)

Reviewed By

Print Name Signature Date