Start up - Air Handling Unit
START-UP SHEET
Air Handling Unit
Job Name Job Number
Job Address
Section 5: Equipment Description
| Spec. #: | Submittal #: | P&ID / Dwg #: |
|---|---|---|
| Area Served: |
| Data | Design | Actual On Site |
|---|---|---|
| Unit Tag # | ||
| Manufacturer | ||
| Model # | ||
| Serial # |
Record filter information below:
| Filter Description | Pre-Filter | Bag Filter | Final Filter |
|---|---|---|---|
| Type | |||
| Size&Quantity | |||
| Size&Quantity |
| Belt Description | | | | | --- | --- | --- | | Size&Quantity | | | |
Section 6: Equipment Pre-Installation Inspection
| Step | Inspection Description | Yes | No | N/A | Performed By(Initials & Date) |
|---|---|---|---|---|---|
| 6.2 | Nameplate data matches vendor specifications. | □ | □ | □ | |
| 6.3 | All parts are received. | □ | □ | □ | |
| 6.4 | No visible signs of damage, leak, or defective parts. | □ | □ | □ |
Comments/
Observations
Performed By
(Therma)
Reviewed By
| Print Name | Signature | Date |
|---|---|---|
(Owner/Representatives)
| Step | Inspection Description | Yes | No | N/A | Performed By(Initials & Date) |
|---|---|---|---|---|---|
| 6.5 | Verify electrical service for correct voltage, current and thermal overload protection. | □ | □ | □ | |
| 6.6 | Operational and Maintenance(O&M) manual is available in the field. | □ | □ | □ | |
| 6.7 | Start-up technicians reviewed factory start-up procedures in the O&M manual. | □ | □ | □ | |
| 6.8 | If Therma provided Variable Frequency Drives(VFDs) that are controlling the fans, complete FN-8029.1 VFD start up form(s). | ||||
| 6.9 | If Therma provided smoke fire dampers use form SFT-Test | □ | □ | □ |
Section 7: Installation Inspection
| Step | Inspection Description | Yes | No | N/A | Performed By(Initials & Date) |
|---|---|---|---|---|---|
| 7.2 | Unit is installed level. | $ | |||
| 7.3 | Tag # is attached to the unit. | $ | |||
| 7.4 | Service clearance is adequate for maintenance. | $ | |||
| 7.5 | Roof curb is installed to mate with the unit. | $ | |||
| 7.6 | All access panels and covers are in place. | $ | |||
| 7.7 | Vibration isolators are installed and adjusted. | $ | |||
| 7.8 | Ductwork and flex connections are connected and sealed. | $ | |||
| 7.9 | Economizer or outside air damper is installed. | $ | |||
| 7.10 | All filters are in place and positioned properly. | $ | |||
| 7.11 | Pressure and temperature taps are installed. | $ | |||
| 7.12 | Heating and cooling coil valves are mounted with actuator. | $ | |||
| 7.13 | Condensate drain and trap are installed. | $ | |||
| 7.14 | Auxiliary drain pan is installed and its connections are piped. | $ | |||
| 7.15 | All piping, coils,and valves are in place without leaks. | $ | |||
| 7.16 | Shipping blocks and materials are removed from fan section. | $ | |||
| 7.17 | Each fan drive belt tension is correct. | $ | |||
| 7.18 | Sheaves are aligned. | $ | |||
| 7.19 | Fan hub,sheaves,and bearing set-screws are tight. | $ | |||
| 7.20 | Smoke detector is installed. | $ | |||
| 7.21 | Motor and blower bearings are lubricated. | $ | |||
| 7.22 | Electrical connections are secure. | $ | |||
| 7.23 | Thermostat is installed. | $ | |||
| 7.24 | Time clock is installed. | $ | |||
| 7.25 | Fan shaft bearings angular alignment is correct and bolts are tight. | $ | |||
| 7.26 | Coils are clean fins are straight. | $ |
| | Print Name | Signature | Date | | --- | --- | --- | | Performed By(Therma) | | | | | Reviewed By(Owner/Representatives) | | | |
START-UP SHEET
Air Handling Unit
Section 8: Operational Inspection
| Step | Inspection Description | Yes | No | N/A | Performed By(Initials & Date) |
|---|---|---|---|---|---|
| 8.2 | Unit vibration is acceptable. | $ | |||
| 8.3 | Each fan rotation is correct. | $ | |||
| 8.4 | Heating water and cooling water control valves are functional. | $ | |||
| 8.5 | Fire dampers are functional and open. | $ | |||
| 8.6 | Supply, return and outside air dampers are functional. | $ | |||
| 8.7 | Smoke detector is tested and is able to shut the unit down. | $ | |||
| 8.8 | Make sure thermostat is set | $ | |||
| 8.9 | Make sure time clock is set | $ | |||
| 8.10 | Record start up operating parameters in the Supplementary Forms(FN 8.028.2 or FN 8.028.3). |
End of Section
Comments/
Observations
| | Print Name | Signature | Date | | --- | --- | --- | | Performed By(Therma) | | | | | Reviewed By(Owner/Representatives) | | | |